Segments static TLS points by BIM object via Scan-vs-BIM. Grid-Square straightedge deviations were directly compared with manual measurements on two aged concrete slabs; F-Numbers were compared only indirectly through rough straightedge equivalences.

技術屬性

欄位內容為文獻擷取紀錄的原文用語(英文),以原文為據;「未查證」表示本站尚未讀到該資訊,不代表該方法不具備此能力。

TLS + BIM floor flatness control 的技術屬性
感測輸入terrestrial laser scanner (FARO Focus3D)
原文測試平台static terrestrial (tripod)
狀態估計不適用
資料關聯Scan-vs-BIM: scans registered to the BIM model (Sec. 4 names the plane-based registration of Bosche (2012) [32], while Sec. 7.3 says the approach of Bosche (2010) [31] was used to register the scans and match the points); each TLS point matched to a BIM object and mesh facet by orthogonal-projection proximity and surface-normal similarity, object recognition from the covered surface; principle credited to Bosche and Haas (2008) [1] (Sec. 4, 5.1.1, 7.3)
時間表示不適用
去畸變不適用
迴圈閉合不適用
全域最佳化不適用
地圖表示point cloud matched to BIM objects
先驗資訊BIM model (Revit, exported as OBJ) of each room (Sec. 7.3)
可輸出幾何per-straightedge maximum deviations (Random, Grid-Square, novel Grid-Star generation) and FF/FL F-Numbers with 90% confidence intervals, linked to BIM objects (Sec. 5-6, 8)
計算需求hardware not reported; Grid-Square flatness control about 10 s; Random and Grid-Star under 15 s (Drainage Lab) and under 2 min (Acoustic Lab); Scan-vs-BIM 25 and 15 min and FARO Scene pre-processing 20 and 10 min, using 10% of the scan data (Sec. 8.1.2, 8.2, Table 5)

使用設備

原文使用的感測器、運算硬體與載具(equipment)。型號保留原文寫法,連結到設備頁中同一型號的歸併名稱;角色依原文用途分為方法輸入、資料集感測器、執行運算平台、參考或真值量測(reference or ground truth)與比較對象設備。

原文使用的設備
類別型號(原文寫法)角色資料集原文規格出處
地面雷射掃描儀(TLS)FARO Focus 3D方法輸入未標示range 0.6 m to 120 m; up to 976,000 points per second; ranging systematic error +/-2 mm at 10 m and 25 m; random error 0.5 mm to 2 mm at 10 m and 25 m (indicative values); scans saved as PTX with FARO Scene; high-accuracy settings made scanning about five times slower than standard(Bosché & Guenet, 2014, Sec. 2.2, 7.3, 8.1.2)
其他2 m long straightedge and precision steel rule on a chalk-line 2 m grid參考或真值量測未標示manual measurement at the same straightedge positions as the Grid-Square layout(Bosché & Guenet, 2014, Sec. 7.2)

優勢、限制與查核補充

以下各點包括文獻擷取紀錄及本站查核補充。原文主張與本站分析請依各點的來源、定位及查核範圍區分;原式或數值的核對不等於完整實驗重現。

優勢

限制

營建工程相關證據

已完工建物中兩片約 25 年的混凝土實驗室樓板(Heriot-Watt 大學,6.40 m × 6.70 m 與 4.80 m × 8.10 m 區段),以人工直尺為獨立參考並比對合格判定;非施工中工地,也非 SLAM 點雲。是具標準化判定與獨立參考的任務方法錨點;是否為本站全部紀錄中唯一者,未經系統檢索確認(推論)。

原文驗證環境:已完工建築、獨立參考量測、任務層驗證

報告的性能數據

以下是原文作者報告的性能數值(author-reported results),不是本站重新量測的結果。每張圖只並列同一個比較組(comparison group,同一張表、同一組實驗設定)內的方法;不同比較組之間的數值不可直接比較,也不構成排名。原表中只由感測器本身得到的基準(例如只用 IMU 的姿態、輪式里程計或 GNSS 接收機的定位結果)不是方法,不列入圖表與紀錄數。

本方法共出現在 6 個比較組,合計 39 筆紀錄。以下列出本方法紀錄最多的 4 組,其餘 2 組列在最後,並連到性能比較頁。

Bosché & Guenet, 2014 · Fig. 13 tables 本方法 12 筆

表格設定(擷取紀錄原文):Maximum and mean 2 m straightedge deviations from the TLS-based system for three straightedge generation methods; Random uses as many straightedges as Grid-Star (230 Acoustic, 320 Drainage); 100% global flatness tolerance 10 mm (Bosché & Guenet, 2014, Fig. 13 tables)

Deviation (mm) Max.,own TLS scans (FARO Focus3D) · Acoustic Lab slab 6.40 m x 6.70 m, two co-registered scans

只並列這張表在相同設定下報告的方法;以「本方法:」開頭者為本頁方法。失敗、未執行與未報告以標記呈現,不是 0。

按 Tab 進入圖表後,用上下方向鍵逐一瀏覽各類別,Esc 關閉提示框;也可開啟表格檢視閱讀全部數值。

這些是 Bosché & Guenet, 2014 在此表設定下報告的數值(author-reported results),只能在同一個比較組內對照,不代表方法在其他資料或設定下的表現。

統計量:最大值(max);對齊方式:原文未報告;單位:mm;場景:completed building: about 25-year-old concrete laboratory floor slabs, Heriot-Watt University

資料來源作者報告值(Bosché & Guenet, 2014, Fig. 13 tables)

數值與出處
方法(原文寫法)報告值出處
Straightedge Grid-Square本方法原文提出7.6 mm(Bosché & Guenet, 2014, Fig. 13 embedded tables (author preprint))
Straightedge Random本方法原文提出11.3 mm(Bosché & Guenet, 2014, Fig. 13 embedded tables (author preprint))
Straightedge Grid-Star (proposed pattern)本方法原文提出11.4 mm(Bosché & Guenet, 2014, Fig. 13 embedded tables (author preprint))

Bosché & Guenet, 2014 · Fig. 12 tables 本方法 10 筆

表格設定(擷取紀錄原文):Grid-Square straightedge (2 m) deviations from the TLS-based system (10% of the initial scans) compared with manual chalk-grid straightedge and steel-rule measurements; paired two-tailed t-test (alpha 0.05, unequal variance as written) (Bosché & Guenet, 2014, Fig. 12 tables)

Difference in straightedge deviation, TLS vs manual: Mean,own TLS scans (FARO Focus3D) · Acoustic Lab slab 6.40 m x 6.70 m, two co-registered scans

這張表在此指標與資料序列只列出本方法一筆,沒有可並列的其他方法,因此不畫圖,數值與出處見下表。這是 Bosché & Guenet, 2014 在此表設定下報告的數值(author-reported results),不代表方法在其他資料或設定下的表現。

統計量:平均值(mean);對齊方式:原文未報告;單位:mm;場景:completed building: about 25-year-old concrete laboratory floor slabs, Heriot-Watt University

數值與出處
方法(原文寫法)報告值出處
Straightedge Grid-Square (TLS-based, Scan-vs-BIM)本方法原文提出1.2 mm(Bosché & Guenet, 2014, Fig. 12 embedded tables (author preprint))

Bosché & Guenet, 2014 · Table 5 本方法 10 筆

表格設定(擷取紀錄原文):Approximate durations of the TLS-based control procedure; processing with 10% of the original scan data; hardware not reported (Bosché & Guenet, 2014, Table 5)

duration: Scan pre-processing (Faro Scene),own TLS scans (FARO Focus3D) · Acoustic Lab slab 6.40 m x 6.70 m, two co-registered scans

這張表在此指標與資料序列只列出本方法一筆,沒有可並列的其他方法,因此不畫圖,數值與出處見下表。這是 Bosché & Guenet, 2014 在此表設定下報告的數值(author-reported results),不代表方法在其他資料或設定下的表現。

統計量:原文未報告;對齊方式:未對齊;單位:min;場景:completed building: about 25-year-old concrete laboratory floor slabs, Heriot-Watt University

數值與出處
方法(原文寫法)報告值出處
TLS-based system (Scan-vs-BIM + Straightedge Grid-Square)本方法原文提出20 min(Bosché & Guenet, 2014, Table 5)

Bosché & Guenet, 2014 · Fig. 14 tables 本方法 4 筆

表格設定(擷取紀錄原文):F-Numbers from the TLS-based ASTM E1155 implementation (10% of the initial TLS data, 90% confidence interval in brackets) compared with the maximum deviation of 3 m Grid-Star straightedges (Bosché & Guenet, 2014, Fig. 14 tables)

Straightedge (3 m Grid-Star) maximum deviation,own TLS scans (FARO Focus3D) · Acoustic Lab slab 6.40 m x 6.70 m, two co-registered scans

這張表在此指標與資料序列只列出本方法一筆,沒有可並列的其他方法,因此不畫圖,數值與出處見下表。這是 Bosché & Guenet, 2014 在此表設定下報告的數值(author-reported results),不代表方法在其他資料或設定下的表現。

統計量:最大值(max);對齊方式:原文未報告;單位:mm;場景:completed building: about 25-year-old concrete laboratory floor slabs, Heriot-Watt University

數值與出處
方法(原文寫法)報告值出處
Straightedge Grid-Star, 3 m本方法原文提出10.8 mm(Bosché & Guenet, 2014, Fig. 14 embedded tables (author preprint))

其他比較組

列出其餘 2 個比較組

來源

  • Bosché & Guenet, 2014

    Frédéric Bosché, Emeline Guenet(2014)Automating surface flatness control using terrestrial laser scanning and building information modelsAutomation in Construction, 44, 212-226

    同儕審查已出版已讀全文公式與數值:部分查核,有疑點經典查證後修正

    查核範圍與原文疑點(2026-10-10)

    Automation in Construction44(2014)212-226 formal HTML and original Figs12-14; official accepted manuscript kept separately

    正式全文已讀;這裡公開獨立原像、正式原文與合成驗算支持的選定統計及驗收界線。沒有原始配對殘差,未重現作者實驗,也未查得當前契約適用標準全文。

    • Section8.1.1 and Fig12 caption / embedded tables:圖說同時稱配對 t 檢定及不等變異數,且未定義差值摘要為有號或絕對差值。若平均/標準差 1.2/1.0 mm 與 0.7/0.4 mm 是 17/10 組有號配對差值,t=平均×√n/標準差會得約 4.948/5.534,無法重現原列 0.57/1.24;摘要的四捨五入也無法消除此條件下的差異。這需要原始配對資料與檢定定義釐清,保留原數字。未拒絕差異假說不等於已證明等價或通過工程驗收。

    • Section5.2.1, straightedge boundary validation:每隔 10 cm 檢查距離邊界至少 40 cm,不能保證一般凹形地坪整條直尺都符合 40 cm 淨距。獨立合成 2 m 線段反例的全部取樣點距邊界至少 0.4021 m,兩點間卻可降至 0.399 m。這是連續淨距保證的界線,不表示作者兩個矩形實驗地坪已發生該失敗。

    • Sections7.1-7.3,8.2-8.3 and Figs13-14:證據來自兩片約 25 年的實驗室樓板與靜態 FARO TLS,人工參考為 17/10 條 2 m 直尺;F-Number 僅與 3 m 直尺的粗略等效關係間接比較。Acoustic 樓板在原文 10 mm 容許差下,Grid-Square 的 7.6 mm 會漏掉 Random/Grid-Star 測得的 11.3/11.4 mm 區域。這說明取樣覆蓋會影響判定,不能直接外推為 SLAM 點雲或當前工程契約驗收通過。

    這些局部檢查未完成所有公式、數值與補充資料的查核,也未獨立重現作者實驗。